Research on Harmonic Overvoltage of Cable Sheath on 220kV Side of Electric Railway Traction Station

Check for updates


Authors

Jinying Cao Affiliation:
State Grid Jiangsu Electric Power Research Institute, Nanjing, 211102, China
, Jie Chen Affiliation:
State Grid Jiangsu Electric Power Research Institute, Nanjing, 211102, China
, Xiao Tan Affiliation:
State Grid Jiangsu Electric Power Research Institute, Nanjing, 211102, China
, Chenying Li Affiliation:
State Grid Jiangsu Electric Power Research Institute, Nanjing, 211102, China
, Wei Zhang Affiliation:
State Grid Jiangsu Electric Power Research Institute, Nanjing, 211102, China
, Chunhua Fang Affiliation:
College of Electrical Engineering and New Energy, Three Gorges University, Yichang, Hubei, 443002, China
, Li Zhuang Affiliation:
College of Electrical Engineering and New Energy, Three Gorges University, Yichang, Hubei, 443002, China
, Yilin Zhang Affiliation:
College of Electrical Engineering and New Energy, Three Gorges University, Yichang, Hubei, 443002, China
and Fang Li Affiliation:
College of Electrical Engineering and New Energy, Three Gorges University, Yichang, Hubei, 443002, China


Abstract

The special operation mode of high-speed railway will generate a large amount of harmonics. The harmonics will be transmitted to the 220kV side high-voltage cables through the traction transformer, and harmonic voltages will be generated on the cable sheath, threatening the safe operation of the cables. In this paper, on the basis of the measured harmonic data of the traction substation, a harmonic source model based on the measured data is established, which solves the complex problem of harmonic source modeling and can accurately reflect the actual operating conditions of high-speed trains. On this basis, the harmonic voltage characteristics of the cable sheath on the 220kV side of the high-speed railway under the three working conditions of traction, regenerative braking and inertia are simulated and calculated, and the effects of cable length, cable grounding method, and harmonic current parameters on the harmonic voltage are explored. Affect the law. The results show that under different operation modes of high-speed rail, the harmonic voltage of the sheath far exceeds the normal operation of the power frequency, and the maximum value of the harmonic voltage of the cable sheath can reach 454V under the traction condition; Under working conditions, the overvoltage of the metal sheath is greatly affected by the grounding method of the cable, the length of the cable and the harmonic current content. The above research results have important reference significance for the safe operation of electrified railways.


Keywords

Over voltage, Railway harmonics, Cable sheath, Influencing factors, 91F99